Difference between revisions of "Seismic Hazard Analysis (Task 6)"
SeismicAdmin (talk | contribs) |
SeismicAdmin (talk | contribs) |
||
| (One intermediate revision by the same user not shown) | |||
| Line 44: | Line 44: | ||
===EPRI Guidance=== | ===EPRI Guidance=== | ||
| − | ''Program on Technology Innovation: Truncation of the Lognormal Distribution and Value of the Standard Deviation for Ground Motion Models in the Central and Eastern United States'', ([ | + | ''Program on Technology Innovation: Truncation of the Lognormal Distribution and Value of the Standard Deviation for Ground Motion Models in the Central and Eastern United States'', ([https://www.epri.com/research/products/000000001013105 1013105]) |
''Central and Eastern United States Seismic Source Characterization for Nuclear Facilities'', ([http://www.ceus-ssc.com/index.htm EPRI 1021097 / NUREG-2115 / DOE/NE-0140]) | ''Central and Eastern United States Seismic Source Characterization for Nuclear Facilities'', ([http://www.ceus-ssc.com/index.htm EPRI 1021097 / NUREG-2115 / DOE/NE-0140]) | ||
| − | ''Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic'', ([ | + | ''Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic'', ([https://www.epri.com/research/products/000000001025287 1025287]) |
| − | ''Central and Eastern United States Seismic Source Characterization for Nuclear Facilities: Review for Reservoir-Induced Seismicity (RIS) in the Southeast and Earthquakes in South Carolina Near the 1886 Charleston Earthquake'', ([ | + | ''Central and Eastern United States Seismic Source Characterization for Nuclear Facilities: Review for Reservoir-Induced Seismicity (RIS) in the Southeast and Earthquakes in South Carolina Near the 1886 Charleston Earthquake'', ([https://www.epri.com/research/products/000000003002005288 3002005288]) |
| − | ''Central and Eastern United States Seismic Source Characterization for Nuclear Facilities: Maximum Magnitude Distribution Evaluation'', ([ | + | ''Central and Eastern United States Seismic Source Characterization for Nuclear Facilities: Maximum Magnitude Distribution Evaluation'', ([https://www.epri.com/research/products/000000003002005684 3002005684]) |
| − | ''EPRI (2004, 2006) Ground-Motion Model (GMM) Review Project'', ([ | + | ''EPRI (2004, 2006) Ground-Motion Model (GMM) Review Project'', ([https://www.epri.com/research/products/000000003002000717 3002000717]) |
| − | ''Seismic Hazard Research: Kappa and High-Frequency Ground Motion Effects at Hard-Rock Sites'', ([ | + | ''Seismic Hazard Research: Kappa and High-Frequency Ground Motion Effects at Hard-Rock Sites'', ([https://www.epri.com/research/products/000000003002020750 3002020750]) |
===Other Guidance=== | ===Other Guidance=== | ||
Latest revision as of 09:45, 30 July 2024
Task Overview
Objective
The objective of this task is to develop seismic hazard curves associated with the plant site.
Purpose
A seismic hazard curve presents the annual frequency (or rate) of exceedance for different values of a selected ground motion parameter (acceleration, velocity, and so on). Hazard curves, which are used as input data in an SPRA, are the final output of a PSHA (probabilistic seismic hazard analysis) representing the mean annual rate of exceedance for the selected motion parameter and the associated uncertainty of this rate at a particular site.
Guidance
An example seismic hazard depicting the annual frequency of exceedance for different values of peak ground acceleration is shown in Figure 6-1. The probability of exceedance of ground motion x means the total probability of the occurrence of all ground motion levels equal to and greater than x. This probability reflects the randomness of future earthquakes; that is, the location, magnitude, and time of the next earthquake to affect the plant is not known. There are generally a number of equally plausible models and interpretations supported by different seismology and geology experts. Each such model produces a different seismic hazard curve. Thus, there is uncertainty about any given result. But the compilation of all such curves would fully represent the state of knowledge about the seismic hazard at the site.
This figure includes the mean hazard curve (average), the 50th percentile curve (which, by definition, indicates that half of the seismic hazard results are below it and half are above), and two typical fractile hazard curves (95% and 5%). The 95th percentile curve indicates that only 5% of the results are above this curve. The 95th percentile curve can be characterized as the confidence (95%) in the hazard estimate (that is, the probability of exceedance of a given ground motion level, x); and 5% of the time, the hazard could be higher.
As shown in Figure 6-2 shows the three key elements that make up the seismic hazard calculation.
- Seismic source characterization describing earthquake source rates, magnitudes, and locations
- Ground motion attenuation characterizing the site ground motion based on the earthquake sources (magnitude, style-of-faulting), the wave propagation (distance), and a general site response (site class or Vs30)
- Site response characterization providing site response functions that account for the site-specific response of the soils below the plant
Seismic sources are typically identified as fault sources or area sources. Fault sources are at identified locations where there are rock fractures or a zone of rock fractures that are known to produce earthquakes. In a seismic source model, they are identified with locations, and a probabilistic distribution of expected magnitudes and recurrence rates. Area sources are regions where earthquake can occur with without defined faults. These area sources are also characterized with a location, or geometric area and a probabilistic distribution of expected magnitudes and recurrence rates.
Seismic ground motion models characterize how earthquake vibrations decay (attenuate) with distance as they travel through rock from the hypocenter to the nuclear plant site. The model also characterizes the resulting ground motion amplitudes (e.g., accelerations), given a specific earthquake magnitude. The ground motion models are also characterized as probabilistic distributions.
A site response model characterizes how the vibrations propagate through the local soils, amplifying or attenuating the motions. These models are developed using site investigations that study the types of soils at the site using bore holes to extract vertical columns of soil as well as various types of vibration propagation measurements. In some studies, the seismic sources are combined with the ground motion model to produce a rock hazard and then the rock hazard is amplified by the site response functions. In more recent studies, the site response is combined with the seismic sources and ground motion model in a composite calculation.
Seismic hazard analyses frequently involve a combination of a number of hazard experts and a variety of potential interpretations. These interactions are frequently performed using a process developed by the Senior Seismic Hazard Analysis Committee (SSHAC) in NUREG/CR-6372, Recommendations for Probabilistic Seismic Hazard Analysis: Guidance on Uncertainty and Use of Experts. The goal of the SSHAC process is to determine the center, body, and range (CBR) of the technically defensible interpretations (TDI), as depicted in Figure 6-3 from NUREG-2213, Updated Implementation Guidelines for SSHAC Hazard Studies.
Supplemental Guidance
Related Element of ASME/PRA Standard
Part 5, Seismic Hazard Analysis (SHA)
EPRI Guidance
Program on Technology Innovation: Truncation of the Lognormal Distribution and Value of the Standard Deviation for Ground Motion Models in the Central and Eastern United States, (1013105)
Central and Eastern United States Seismic Source Characterization for Nuclear Facilities, (EPRI 1021097 / NUREG-2115 / DOE/NE-0140)
Seismic Evaluation Guidance: Screening, Prioritization and Implementation Details (SPID) for the Resolution of Fukushima Near-Term Task Force Recommendation 2.1: Seismic, (1025287)
Central and Eastern United States Seismic Source Characterization for Nuclear Facilities: Review for Reservoir-Induced Seismicity (RIS) in the Southeast and Earthquakes in South Carolina Near the 1886 Charleston Earthquake, (3002005288)
Central and Eastern United States Seismic Source Characterization for Nuclear Facilities: Maximum Magnitude Distribution Evaluation, (3002005684)
EPRI (2004, 2006) Ground-Motion Model (GMM) Review Project, (3002000717)
Seismic Hazard Research: Kappa and High-Frequency Ground Motion Effects at Hard-Rock Sites, (3002020750)
Other Guidance
NUREG/CR-6372, Recommendations for Probabilistic Seismic Hazard Analysis: Guidance on Uncertainty and Use of Experts
NUREG/CR-6728, Technical Basis for Revision of Regulatory Guidance on Ground Motions: Hazard- and Risk-consistent Ground Motion Spectra Guidelines
Regulatory Guide 1.208, A Performance-Based Approach to Define the Site-Specific Earthquake Ground Motion
NUREG-2213, Updated Implementation Guidelines for SSHAC Hazard Studies
Pacific Earthquake Engineering Research Center (PEER) 2018/08, Central and Eastern North America Ground-Motion Characterization: NGA-East Final Report